D–FRU Replacement
QLogic 12800 Series
D000102-000 B D-11
Spine Module Replacement
FRU part number:
Single Spine Module: 12800-SPSG01-9X
Double Spine Module: 12800-SPDB01-9X
Removal Procedures
1. Pull the release arms out until the spine module disengages from the
backplane connector.
Figure D-7 .12800 Spine Removal
2. Carefully pull the module out of the chassis.
Replacement Procedures
1. Slide the module straight into the open slot until it engages with the
backplane connector.
2. Push the arm up until they lock in place.
3. Make sure the module is operating and the Status LED(s) is green.